FILTER CLASS(EN1822)
|
H11
|
H13
|
H14
|
U15
|
Global Efficiency % for MPPS
|
≥95%
|
≥99.95%
|
≥99.995%
|
≥99.9995%
|
Local Efficiency % for MPPS
|
-
|
99.75%
|
99.98%
|
99.9975%
|
Recommended Final Pressure Drop
|
600Pa
|
600Pa
|
600Pa
|
600Pa
|
Max.Final Pressure Drop
|
1000Pa
|
1000Pa
|
1000Pa
|
1000Pa
|
Continuous Temperature Resistance
|
80℃
|
80℃
|
80℃
|
80℃
|
Max.Relative Humidity Resistance
|
100%
|
100%
|
100%
|
100%
|
Frame
|
Aluminium and MDF
|
Face Guard
|
Epoxy painted expanded aluminium grids on both sides
|
Gasket
|
One piece foamed polyurethane
|
Fire Resistance Class
|
K1/F1 according to DIN53438
|
Filter Stage
|
III
|
TESTING
|
Each filter individually tested according to EN 1822
|
For MDF Frame filter one and two side with protective girds optional
|